Notifier RP-2002C User Manual

Browse online or download User Manual for Safety Notifier RP-2002C. Notifier RP-2002C User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
DN-60444:B1 • 12/22/11 — Page 1 of 4
RP-2002C
Agent Release Control Panel
Conventional Releasing Panels
Canadian DN-60444:B1
General
The RP-2002C is a six-zone FACP for single and dual hazard
agent releasing applications. The RP-2002C provides reliable
fire detection, signaling and protection for commercial, indus-
trial and institutional buildings requiring agent-based releasing.
The RP-2002C is compatible with System Sensor’s i
3
detec-
tors which are conventional smoke detectors that can transmit
a maintenance trouble signal to the FACP indicating the need
for cleaning and a supervisory ‘freeze’ signal when the ambi-
ent temperature falls below the detector rating of approxi-
mately 7.22°C. In addition, the control panel is compatible with
conventional input devices such as two-wire smoke detectors,
four-wire smoke detectors, pull stations, waterflow devices,
tamper switches and other normally-open contact devices.
Refer to the Notifier Device Compatibility Document for a com-
plete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli-
ance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The RP-2002C supervises all wiring, AC voltage,
battery charger and battery level.
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm infor-
mation on the panel’s LCD, sound the piezo sounder at the
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary
control function.
Features
Listed to Standard ULC-S527-99.
Designed for agent releasing standards NFPA 12, 12A, 12B,
and 2001.
Meets International Building Code (IBC) seismic require-
ments.
Disable/Enable control per input zone and output zone.
Extensive transient protection.
Dual hazard operation.
Adjustable pre-discharge, discharge and waterflow delay
timers.
Cross-zone (double-interlock) capability.
Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
System Sensor i
3
series detector compatible.
Four programmable Style Y (Class B) output circuits - (spe-
cial application power).
Strobe synchronization:
System Sensor
Wheelock
Three programmable Form-C relays.
7.0 amps total 24 VDC output current.
Resettable and non-resettable output power.
Built-in Programmer.
ANN-BUS for connection to optional devices (up to 8 total of
any of the following):
N-ANN-80 Remote LCD Annunciator
N-ANN-I/O LED Driver
N-ANN-S/PG Printer Module (only one allowed per panel)
N-ANN-RLY Relay Module
N-ANN-LED Annunciator Module (built-in)
80-character LCD display (backlit).
Real-time clock/calendar with daylight savings time control.
History log with 256 event storage.
Piezo sounder for alarm, trouble and supervisory.
24 volt operation.
Low AC voltage sense.
Outputs Programmable for:
Releasing Circuits or NACS
NACs programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Non-silenceable
Release Stage Sounder
Automatic battery charger with charger supervision.
Optional Trim Ring TR-CE (red) for semi-flush mounting the
cabinet.
Optional N-CAC-5X Class A Converter Module for Outputs
and IDCs.
Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD,
411UDAC).
Optional ANN-SEC card for a secondary ANN-BUS
Page view 0
1 2 3 4

Summary of Contents

Page 1 - RP-2002C

DN-60444:B1 • 12/22/11 — Page 1 of 4RP-2002CAgent Release Control PanelConventional Releasing PanelsCanadian DN-60444:B1GeneralThe RP-2002C is a six-z

Page 2 - Controls and Indicators

Page 2 of 4 — Canadian DN-60444:B1 • 12/22/11PROGRAMMING AND SOFTWARE:• Custom English labels (per point) may be manually enteredor selected from an i

Page 3 - Product Line Information

Canadian DN-60444:B1 • 12/22/11 — Page 3 of 4Product Line InformationRP-2002C: Six-zone, 24 volt Agent Release Control Panel(includes backbox, power

Page 4 - SYSTEM SPECIFICATIONS

System Capacity• Annunciators .............. .....2Electrical Specifications• RP-2002C: (FLPS-7 Pow