DN-7006 • 05/09/05 — Page 1 of 4
GENERAL
ND-100 and ND100R photoelectric duct smoke detectors are
used exclusively with the NOTIFIER FireWarden-100 (NFW-
100) addressable control panel. They provide low-flow tech-
nology that enables duct smoke detection throughout a broad
range of airflow environments in HVAC applications. The low-
flow technology can detect smoke at air speed velocities of
100 feet per minute (0.5 m/sec) or greater, while continuing
the same reliable performance to 4,000 feet per minute (20.32
m/sec). The intelligent low-flow duct detectors sample air cur-
rents passing through a duct and gives dependable perfor-
mance for shutdown of fans, blowers, and air conditioning
systems, preventing the spread of toxic smoke an fire gases
through the protected area.
ND-100 and ND-100R provide a remote alarm output for use
with auxiliary devices, such as the RA400 remote LED annun-
ciator, as well as remote test capability with the RTS451 or
RTS451KEY Remote Test Stations. The ND-100R features a
Form-C relay.
APPLICATIONS
Duct smoke detectors have specific limitations, they are:
NOT
a substitute for open area smoke detectors.
NOT
a substitute for early warning detection.
NOT
a replacement for a building’s regular fire detection
system.
Please call NOTIFIER for a copy of System Sensor’s applica-
tion guide,
Proper Use of Smoke Detectors in Duct Applica-
tions
, (A05-1004-00).
FEATURES
Air velocity rating from 100 to 4,000 feet per minute (0.5 to
20.32 m/sec).
Patented telescopic sampling tube.
Easily accessible code wheels for addressing detector.
Outside mounting tabs.
Mounts to round or rectangular ducts from 1’ to 12’ (0.3 to 3.7
meters) wide.
Transparent cover for convenient visual inspection.
Powered outputs for remote LED, and remote test and
sounder.
Two Form-C auxiliary contacts (ND-100R).
Patented cover-tamper trouble signal.
ND-100R requires both com line power and one of the
following: 24 VAC/VDC or 120/220 VAC for operation.
INSTALLATION
Refer to installation manuals for control panel and duct
detector for detailed information or to install equipment.
Wiring: For signal wiring (the wiring between detectors or
from detectors to auxiliary devices), it is recommended that
single conductor wire be no smaller than 18 AWG (0.78 mm²).
The duct smoke detector terminals accommodate wire sizes
up to 12 AWG (3.1 mm²). Flexible conduit is recommended for
the last foot (30.48 cm) of conduit; solid conduit connections
may be used if desired.
Smoke detectors and alarm system control panels have speci-
fications for Signaling Line Circuit (SLC) wiring. Consult the
control panel specifications for wiring requirements before
wiring the detector loop. The ND-100 and ND-100R detectors
are designed for ease of wiring; their housing provides a ter-
minal strip with clamping plates.
6955pl.jpg
ND-100
ND-100 and ND-100R
Low-Flow Photoelectric Duct Smoke
Detectors for FireWarden-100
Section: Addressable
DN-7006 • A1-340
May 9, 2005
S635
California
State Fire
Marshal
3240-0028:232
(ND-100R)
3240-0028:236
(ND-100)
MEA
320-02-E Vol. II
(ND-100R)
Permit # 2173
(ND-100R)
MARYLAND
State Fire Marshal
6955rpl.jpg
ND-100R
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
Page view 0
1 2 3 4

Summary of Contents

Page 1 - ND-100 and ND-100R

DN-7006 • 05/09/05 — Page 1 of 4GENERALND-100 and ND100R photoelectric duct smoke detectors areused exclusively with the NOTIFIER FireWarden-100 (NFW

Page 2 - Power supply voltage

Page 2 of 4 — DN-7006 • 05/09/05SPECIFICATIONSND-100Operating voltage range: 15 to 30 VDC.Standby current: 300 µA @ 24 VDC (one communicationevery 5

Page 3 - For RTS451KEY

DN-7006 • 05/09/05 — Page 3 of 4WIRING DIAGRAMS for ND-100*NOTE: Inlet tube is required and must be purchased separately.Order one inlet tube for eac

Page 4 - WIRING DIAGRAMS for ND-100R

Page 4 of 4 — DN-7006 • 05/09/05WIRING DIAGRAMS for ND-100RND-100R Duct Smoke Detector using a UL-Listed control panel:7006wir1.wmfNOTES: 1) Jumper