DN-6940:B1 • 8/31/2011 — Page 3 of 4
Signals Silenced (yellow) illuminates if notification appli-
ances have been silenced. It flashes if some, but not all, of the
NACs have been silenced.
Point Disabled (yellow) illuminates when at least one device
has been disabled. It will flash until all disabled points have
been acknowledged.
Controls Active (green) illuminates when the LCD-160
assumes control of the node as a primary display.
DIAGNOSTIC LED INDICATORS
Status, LED11 (green), blinks when the LCD-160 is on. Visi-
ble to the installer/troubleshooter only.
Receive, LED12 (green), blinks when data is received from
the panel. Visible to the installer/troubleshooter only.
Transmit, LED13 (green), blinks when data is transmitted to
the panel. Visible to the installer/troubleshooter only.
Microfail, LED14 (yellow), illuminates if the microcontroller
fails. Visible to the installer/troubleshooter only.
Event Handling and the
Display and Control Center
UL and ULC require that when multiple command and control
centers are installed, only one operator at any location can be
in control at any given time for functions such as acknowledge,
silence, and reset. This is called the Display and Control Cen-
ter (DCC). DCC operation provides a mechanism to pass net-
work control to alternate network control centers. This protocol
allows for a “request for control” from another networked
panel, which will be accepted or rejected from the current
DCC. A 15-second time-out allowance provides for an auto-
matic passing of control in the event there is no response from
the original DCC. If the NFS-3030/NFS2-3030 panel associ-
ated with an LCD-160 has been programmed to participate in
DCC, all remote displays with Local Control ON will automati-
cally participate.
Agency Listings and Approvals
These listings and approvals apply to the LCD-160. In some
cases, certain modules or applications may not be listed by
certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
UL: S635
ULC: S635
MEA: 8-04-E (annunciator only)
FDNY: COA#6065 (with NFS2-3030)
CSFM: 7120-0028:0227, 7165-0028:0224
FM Approved
RDP Bus Wire Runs