DN-6720:C • 10/06/2010 — Page 1 of 4
FMM-1(A), FMM-101(A),
FZM-1(A) & FDM-1(A)
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
DN-6720:C • H-220
General
Four different monitor modules are available for Notifier’s intel-
ligent control panels for a variety of applications. Monitor mod-
ules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Style D (Class
A) or Style B (Class B) circuit of dry-contact input devices.
FMM-101(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that super-
vises a Style B (Class B) circuit of dry-contact input devices.
Its compact design allows the FMM-101(A) to be mounted in a
single-gang box behind the device it monitors.
FZM-1(A) is a standard-sized module that monitors and super-
vises compatible two-wire, 24 volt, smoke detectors on a Style
D (Class A) or Style B (Class B) circuit.
FDM-1(A) is a standard-sized dual monitor module that moni-
tors and supervises two independent two-wire Style B (Class
B) dry-contact initiating device circuits (IDCs) at two
separate,
consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by NOTIFIER that greatly increases the speed
of communication between analog intelligent devices. Intelli-
gent devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
FMM-1(A) Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
LED flashes green during normal operation (this is a pro-
grammable option) and latches on steady red to indicate
alarm.
The FMM-1(A) Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.
FMM-1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-
tions on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FMM-1(A) (Type H)
6999cov.jpg
Page view 0
1 2 3 4

Summary of Contents

Page 1 - FZM-1(A) & FDM-1(A)

DN-6720:C • 10/06/2010 — Page 1 of 4FMM-1(A), FMM-101(A),FZM-1(A) & FDM-1(A)Monitor Modules with FlashScan®Intelligent/Addressable DevicesDN-6720:

Page 2 - FZM-1(A) Interface Module

Page 2 of 4 — DN-6720:C • 10/06/2010FMM-101(A) Mini Monitor Module• Built-in type identification automatically identifies this deviceas a monitor modu

Page 3 - Product Line Information

DN-6720:C • 10/06/2010 — Page 3 of 4FDM1(A) Dual Monitor ModuleThe FDM-1(A) Dual Monitor Module is intended for use in intelli-gent, two-wire systems.

Page 4

Page 4 of 4 — DN-6720:C • 10/06/2010FlashScan® and NOTIFIER® are registered trademarks and FireWatch™ isa trademark of Honeywell International Inc.©20