DN-60327:B1 • 11/9/11 — Page 1 of 2
SpectrAlert® Advance
Indoor Selectable Output Speaker Strobes and
Dual Voltage Evacuation Speakers
Audio/Visual Devices
DN-60327:B1
General
The SpectrAlert Advance Series of speakers and speaker
strobes is designed to reduce ground faults. The plug-in design
allows the installer to pre-wire mounting plates and dress the
wires before plugging in the speakers. The plastic cover pre-
vents nicked wires by covering exposed speaker components.
This design also allows faster installations with instant feedback
to ensure that wiring is properly connected; rotary switches to
select voltage and power settings; and 11 field selectable can-
dela settings for wall and ceiling speaker strobes.
The low total harmonic distortion of the SP speaker offers high
fidelity sound output while the SPV speaker offers high volume
sound output for use in high ambient noise applications.
SpectrAlert Advance makes installation easy
Attach a universal mounting plate to a 4” x 4” x 2-1/8” back
box. Flush mount applications are achievable without the
need for an extension ring.
Connect the notification appliance circuit or speaker wiring to
the PEMS terminals on the mounting plate.
Attach the speaker or speaker strobe to the mounting plate
by inserting the product tabs into the mounting plate grooves.
Rotate the device into position to lock the product pins into
the mounting plate terminals. The device will temporarily hold
in place with a catch until it is secured with a captured mount-
ing screw.
Features
Plug-in design
Protective cover isolates speaker components, reduces
ground faults
Electrical compatibility with existing SpectrAlert products
Field selectable candela settings on wall and ceiling units:
Standard: 15, 15/75, 30, 75, 95, 110, 115
High: 135, 150, 177, 185
Shorting spring on mounting plate tests continuity before
installation
Rotary switch simplifies field selection of speaker voltage and
power settings
Universal mounting plate for wall- and ceiling-mount units
Compatible with System Sensor synchronization protocol
SP speakers offer high fidelity sound output
SPV speakers offer high volume sound output
Automatic selection of 12 or 24 volt operation at 15 and 15/75
candela
No extension ring required
Ceiling and wall mount application
Optional tamper resistant Torx head screw included
Specifications
PHYSICAL SPECIFICATIONS
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
Dimensions, Wall-Mount: –
SPS Speaker Strobe: 6.0”L x 5.0”W x 4.7”D (includes lens
and speaker)
SPSV Speaker Strobe: 6.0”L x 5.0”W x 4.9”D (includes
lens and speaker)
SP Speaker: 6.0”L x 5.0”W x 2.8”D
SPSV Speaker: 6.0”L x 5.0”W x 2.9”D
Dimensions, Ceiling-Mount:
SPS Speaker Strobe: 6.8”Dia x 4.7”D (includes lens and
speaker)
SPSV Speaker Strobe: 6.8”Dia x 4.8”D (includes lens and
speaker)
SP Speaker: 6.8”Dia x 2.8”D
SPSV Speaker: 6.8”Dia x 2.9”D
ELECTRICAL/OPERATING SPECIFICATIONS
Nominal Voltage (speakers): 25 Volts or 70.7 Volts
(nominal)
Maximum Supervisory Voltage (speakers): 50VDC
Strobe Flash Rate: 1 flash per second
Nominal Voltage (strobes): Regulated 12VDC/FWR or regu-
lated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with
built-in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V
nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V
nominal) or 17 to 33V (24V nominal)
Frequency Range: 400 to 4000 Hz
Power: ¼, ½, 1, 2 watts
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in progress. Consult fac-
tory for latest listing status.
UL/ULC Listed: S4048
MEA: 10-08-E
CSFM: 7320-1653:201
FM Approved
6
0
3
2
7
p
h
o
1
.
j
p
g
Page view 0
1 2

Summary of Contents

Page 1 - SpectrAlert® Advance

DN-60327:B1 • 11/9/11 — Page 1 of 2SpectrAlert® AdvanceIndoor Selectable Output Speaker Strobes andDual Voltage Evacuation SpeakersAudio/Visual Device

Page 2 - Ordering Information

Page 2 of 2 — DN-60327:B1 • 11/9/11SpectrAlert® is a registered trademark of Honeywell International Inc. ©2011 by Honeywell International Inc. All ri

Comments to this Manuals

No comments